Test cases for a lift / elevator
Updated 2026-11-13 · 6 min read
Testing a lift is a favourite interview prompt for checking how you think. These 32 cases cover calls and travel, doors, load, emergencies, access control, accessibility and performance.
Assumes a passenger lift in a ground-plus-ten building (floors G to 10, plus one basement for parking), with car buttons, up and down landing buttons, door open and close buttons, an alarm button, an overload sensor and an access-card reader for the basement and floor 10.
How to answer in an interview
Ask before listing: how many floors and lifts, the rated load (from the plate inside the car), whether lifts work as a group, which floors are restricted, and what must happen on a power cut or fire alarm. Say that safety certification is done by authorised inspectors, and that your cases cover the controller's behaviour. Then group: calls and travel, doors, load, emergencies, access, accessibility and performance.
Scope and test data
Physical safety checks (brakes, ropes, landing door locks) are for qualified lift technicians; where a case below touches them, it is written as "observed during the technician's inspection". Use a soft foam block, not a hand, for door obstruction tests, and test weights for load tests. Waiting-time and levelling limits must come from the installer's specification before these cases can pass or fail. These are designed cases, not an execution report.
Calls and travel
| ID | Category | Test case | Expected result |
|---|---|---|---|
| E01 | Functional | Lift idle at G; press Up on floor 3 | Lift travels to 3, Up arrow lights, doors open |
| E02 | Functional | Inside the car, press 7 | Lift travels to 7, stops level, doors open, display shows 7 |
| E03 | Functional | Press the button for the floor the lift is already on | Doors open (or stay open); no travel |
| E04 | Functional | From G going up, press 8, then 2, then 5 | Stops at 2, 5 and 8 in that order (direction order), unless the spec says otherwise |
| E05 | Functional | On floor 4, press Up and Down while the lift passes going up | Lift stops for Up on the way up; the Down call is served on the way back |
| E06 | Boundary | Look at the landing panels on floor 10 and in the basement | Floor 10 has no Up button; the basement has no Down button |
| E07 | Boundary | Travel to the top floor and to the basement | Lift stops level at both ends and never overruns |
| E08 | Negative | Press B (basement) without showing an access card | Call is not registered, or the panel asks for a card |
| E09 | Functional | Press a car button twice to cancel it, if the lift supports cancelling | Call is cancelled and the light goes off; if unsupported, nothing changes |
| E10 | Functional | Leave the lift with no calls for the idle period | Parks at its home floor if configured; doors closed; car fan and light switch off as specified |
Doors
| ID | Category | Test case | Expected result |
|---|---|---|---|
| E11 | Functional | Press Door Open while the doors are closing | Doors reopen |
| E12 | Functional | Press Door Close after the doors open | Doors close sooner, or the button is ignored, as specified |
| E13 | Functional | Put a foam block in the door path while the doors close | Doors reverse before pressing hard on the block |
| E14 | Negative | Hold the doors open past the timeout | Buzzer sounds; doors close slowly (nudging) if that feature exists |
| E15 | Functional | Try to make the lift travel with the car door held open | Lift does not move while any door is open |
| E16 | Functional | Observed during the technician's inspection: try the landing door on a floor where the car is not present | Landing door stays locked |
Load
| ID | Category | Test case | Expected result |
|---|---|---|---|
| E17 | Boundary | Load the car to its rated load with test weights | Travels normally |
| E18 | Boundary | Add weight just above the rated load | Overload buzzer and indicator; doors stay open; lift does not move |
| E19 | Functional | Remove the extra weight | Overload warning clears; lift accepts calls again |
Emergencies and service modes
| ID | Category | Test case | Expected result |
|---|---|---|---|
| E20 | Functional | Press and hold the alarm button | Alarm sounds and the intercom reaches security or the monitoring desk within the agreed time |
| E21 | Negative | Cut mains power while the lift travels between floors | Emergency light works; if a rescue device is fitted, the car moves to the nearest floor and opens its doors |
| E22 | Functional | Trigger the fire alarm signal in a controlled test | Lift goes to the designated floor, opens its doors and ignores normal calls, as the local code and spec require |
| E23 | Negative | Simulate a fault that stops the car between floors | Doors do not open between floors; alarm and intercom still work; the fault is logged |
| E24 | Functional | Technician switches the lift to maintenance mode | Landing calls ignored; landing displays show it is out of service |
Access, accessibility and UI
| ID | Category | Test case | Expected result |
|---|---|---|---|
| E25 | Security | Show a card allowed for floor 10 only and press B | B refused; 10 accepted |
| E26 | Security | Show an expired or blocked card | All restricted floors refused; event logged |
| E27 | UI | Ride from G to 10 and back | Car and landing displays show the correct floor and direction at every floor |
| E28 | UI | Arrive at a floor | Chime and voice announcement (if fitted) name the floor |
| E29 | UI | Check button height and markings | Buttons reachable from a wheelchair; raised or Braille markings as specified |
| E30 | UI | Press any button | It lights on press and goes off when the call is served |
Performance
| ID | Category | Test case | Expected result |
|---|---|---|---|
| E31 | Performance | Morning peak simulation: many up calls from G with all lifts in service | Group control sends a suitable car; waiting time stays within the installer's figure |
| E32 | Performance | Measure the step between car floor and landing at several floors, empty and loaded | Within the installer's levelling tolerance |
What to prioritise
The cases that protect people come first: doors (E13, E15, E16), overload (E18) and emergencies (E20 to E23). A common mistake is to spend the whole answer on buttons and displays. Another is to forget the multiple-lift case: with two or more lifts, "which lift answers my call" is a requirement you should ask about.
Downloads
Quick answers
Would a software tester really test a lift?
Not its safety certification: that is done by the installer and authorised inspectors under local rules. The question checks whether you can find behaviours, boundaries and failure cases for any system. Say that early, then answer as if you were testing the lift controller's behaviour.
Should the lift stop at floors in the order the buttons were pressed?
Usually not. Most passenger lifts serve calls in the direction of travel (collective control), so pressing 8, 2 and 5 going up gives stops at 2, 5 and 8. Ask which control logic the lift uses rather than assuming.